i.3

Modified Parameters

u

H1: Multi-Function Digital Inputs

n

H1-03 to H1-07: Functions for Terminals S3 to S7

These parameters assign functions to the multi-function digital inputs.

Note:

Setting F is added and Setting 13 is removed for parameters H1-03 to H1-07 in bypass controller software versions VST800298 and later.

No.

Addr.

Hex

Parameter Name

Setting

Range

Default

H1-03

(0400)

Multi-Function Digital Input Terminal S3 Function Selection

3 to 60

24: External Fault

H1-04

(0401)

Multi-Function Digital Input Terminal S4 Function Selection

3 to 60

14: Fault Reset

H1-05

(0402)

Multi-Function Digital Input Terminal S5 Function Selection

3 to 60

3: Multi-Step Speed Reference 1

H1-06

(0403)

Multi-Function Digital Input Terminal S6 Function Selection

3 to 60

4: Multi-Step Speed Reference 2

H1-07

(0404)

Multi-Function Digital Input Terminal S7 Function Selection

3 to 60

6: Jog Reference Selection

Table i.3 Added Multi-Function Digital Input Terminal Setting

Setting

Function

F

Not Used (Through Mode)

Setting F: Not Used (Through Mode)

Select this setting when using the terminal in a pass-through mode. When set to F, an input does not trigger any function in

the drive. Setting F, however, still allows the input status to be read out by a PLC via a communication option or MEMOBUS/

Modbus communications.

Table i.4 Removed Multi-Function Digital Input Terminal Setting

Setting

Function

13

Jog Reverse

u

H3: Multi-Function Analog Inputs

These parameters assign functions to multi-function analog input terminals: A1 and A2.

n

H3-oo Multi-Function Analog Input Terminal Settings

Note:

Setting 1F is “HAND Reference” in bypass controller software versions VST800298 and later. Setting 1F is “Not Used (Through Mode)”

in bypass controller software versions VST800297 and earlier.

Table i.5 Modified Multi-Function Analog Input Terminal Setting

Setting

Function

1F

HAND Reference

Setting 1F: HAND Reference

Sets the frequency reference when in HAND Mode and parameter Z1-41, HAND Speed Reference Selection, is set to 1

(Analog).

u

L2: Momentary Power Loss Ride-Thru

n

L2-01: Momentary Power Loss Operation Selection

When a momentary power loss occurs (DC bus voltage falls below the level set in L2-05), the drive can automatically return

to the operation it was performing prior to the power loss based on certain conditions.

Note:

Default is 2 in bypass controller software versions VST800298 and later. Default is 0 in bypass controller software versions VST800297

and earlier.

i.3 Modified Parameters