New Parameters and New Monitor

u

H2: Multi-Function Digital Outputs

Note:

H2-oo parameters are available in bypass controller software versions VST800298 and later.

n

H2-01 to H2-03: Terminal M1-M2, M3-M4, and M5-M6 Function Selection

The bypass has three multi-function output terminals.

Table i.2

lists the functions available for these terminals using H2-01,

H2-02, and H2-03.

No.

Addr.

Hex

Parameter Name

Setting Range

Default

H2-01

(040B)

Terminal M1-M2 Function Selection (relay)

0 to 160

0: During Run 1

H2-02

(040C)

Terminal M3-M4 Function Selection (relay)

0 to 160

1: Zero Speed

H2-03

(040D)

Terminal M5-M6 Function Selection (relay)

0 to 160

2: Speed Agree 1

Table i.2 Multi-Function Digital Output Terminal Settings

Setting

Function

Page

0

During Run 1

5

1

Zero Speed

6

2

Speed Agree 1

6

3

User-Set Speed Agree 1

6

4

Frequency Detection 1

7

5

Frequency Detection 2

7

6

Drive Ready

8

7

DC Bus Undervoltage

8

8

During Baseblock 1 (N.O.)

8

B

Torque Detection 1 (N.O.)

8

C

Frequency Reference Loss

8

E

Fault

8

F

Through Mode

9

10

Minor Fault

9

11

Fault Reset Command Active

9

13

Speed Agree 2

9

Setting

Function

Page

14

User-Set Speed Agree 2

9

15

Frequency Detection 3

10

16

Frequency Detection 4

10

17

Torque Detection 1 (N.C.)

8

1A

During Reverse

11

1B

During Baseblock 2 (N.C.)

11

1E

Restart Enabled

11

20

Drive Overheat Pre-Alarm (oH)

11

2F

Maintenance Period

11

37

During Run 2

11

39

Watt Hour Pulse Output

12

3D

During Speed Search

12

4C

During Fast Stop

12

4D

oH Pre-Alarm Time Limit

12

60

Internal Cooling Fan Alarm

12

100 to 160 Functions 0 to 60 with Inverse Output

12

Setting 0: During Run

The output closes when the drive is outputting a voltage.

Status

Description

Open

Drive is stopped.

Closed

A Run command is input or the drive is in deceleration or DC injection.

ON

ON

OFF

OFF

ON

OFF

Run command

Baseblock

command

Output

frequency

During Run

Figure i.1 During Run Time Chart

i.2 New Parameters and New Monitor