Setting 1: Zero Speed

The output closes when the output frequency or motor speed falls below the minimum output frequency set to E1-09 or b2-01.

Status

Description

Open

Output frequency is above the minimum output frequency set to E1-09 or b2-01

Closed

Output frequency is less than the minimum output frequency set to E1-09 or b2-01

OFF

Output frequency

or

motor speed

Zero Speed

ON

E1-09 (Max. Output Frequency) or
b2-01 (Zero Speed Level)

Figure i.2 Zero-Speed Time Chart

Setting 2: Speed Agree 1 (f

ref

/f

out

Agree 1)

The output closes when the actual output frequency or motor speed is within the Speed Agree Width (L4-02) of the current

frequency reference regardless of the direction.

Status

Description

Open

Output frequency or motor speed does not match the frequency reference while the drive is running.

Closed

Output frequency or motor speed is within the range of frequency reference ±L4-02.

Note:

Detection works in forward and reverse.

L4-02

L4-02

Frequency
reference

Speed agree 1

ON

OFF

Output Frequency

or Motor Speed

Figure i.3 Speed Agree 1 Time Chart

Setting 3: User-Set Speed Agree 1 (f

ref

/f

set

Agree 1)

The output closes when the actual output frequency or motor speed and the frequency reference are within the speed agree

width (L4-02) of the programmed speed agree level (L4-01).

Status

Description

Open

Output frequency or motor speed and frequency reference are not both within the range of L4-01 ±L4-02.

Closed

Output frequency or motor speed and the frequency reference are both within the range of L4-01 ±L4-02.

Note:

Frequency detection works in forward and reverse. The value of L4-01 is used as the detection level for both directions.

i.2 New Parameters and New Monitor

6

YASKAWA TOEP YAISUP 06A YASKAWA AC Drive – Z1000 Bypass Manual Supplement