Z2: bypass control input/output – Yaskawa AC Drive Z1000 AC Drive Bypass for HVAC User Manual

Page 18

Advertising
background image

No.

Addr. Hex

Name

Setting Range

Default

Z1-37

(853A)

Set Time

0 to 2

0

Setting 0: Normal Display
Setting 1: Displays Time and Date Setting Mode
Setting 2: Reset Time

u

Z2: Bypass Control Input/Output

n

Z2-01 to Z2-08: Digital Input 1 to 8 Function Select

Note:

Setting 22 for parameters Z2-01 to Z2-08 is modified in bypass controller software version VST800298.

No.

Addr. Hex

Name

Setting Range

Default

Z2-01

(8563)

Digital Input 1 Function Select

0 to 36

21

Z2-02

(8564)

Digital Input 2 Function Select

0 to 36

22

Z2-03

(8565)

Digital Input 3 Function Select

0 to 36

23

Z2-04

(8566)

Digital Input 4 Function Select

0 to 36

24

Z2-05

(8567)

Digital Input 5 Function Select

0 to 36

25

Z2-06

(8568)

Digital Input 6 Function Select

0 to 36

0

Z2-07

(8569)

Digital Input 7 Function Select

0 to 36

0

Z2-08

(856A)

Digital Input 8 Function Select

0 to 36

29

Table i.6 Modified Bypass Digital Input Terminal Setting

Setting

Function

22

Run Enable (Safety)

Note:

In bypass controller software versions VST800298 and later, multiple digital input terminals can be

programmed for “Run Enable (Safety)” (Z2-0o = 22). The drive will run only when all digital inputs

programmed for “22” are active.

n

Z2-23 to Z2-26: Digital Output 7 to 10 Function Select

Note:

Setting 23 for parameters Z2-23 to Z2-26 is added in bypass controller software version VST800298. Setting 23 is not available in bypass

controller software versions VST800297 and earlier.

No.

Addr. Hex

Name

Setting Range

Default

Z2-23

(8579)

Digital Output 7 Function Select

0 to 23; 99

7

Z2-24

(857A)

Digital Output 8 Function Select

0 to 23; 99

10

Z2-25

(857B)

Digital Output 9 Function Select

0 to 23; 99

12

Z2-26

(857C)

Digital Output 10 Function Select

0 to 23; 99

15

Table i.7 Added Bypass Digital Output Terminal Setting

Setting

Function

23

Run Verify

The digital output closes when the drive or bypass output current exceeds 10% of the value set in E2-01.

The digital output opens when the drive or bypass output current falls below 5% of the value set in E2-01.

i.3 Modified Parameters

18

YASKAWA TOEP YAISUP 06A YASKAWA AC Drive – Z1000 Bypass Manual Supplement