New and modified faults and alarms, New faults and alarms, Modified fault – Yaskawa AC Drive Z1000 AC Drive Bypass for HVAC User Manual

Page 20: I.5 new and modified faults and alarms

Advertising
background image

i.5

New and Modified Faults and Alarms

u

New Faults and Alarms

Note:

Faults and alarms in this section are added in bypass controller software version VST800298.

HOA Keypad Display

Minor Fault Name

AL16

Input Phase Rotation

Cause

Possible Solution

Incorrect phase rotation while Z1-52 is set to 1 in

Bypass Mode.

Check the sequence (phase rotation) of the input wiring to the bypass package.

HOA Keypad Display

Fault Name

FB15

Input Phase Loss

Cause

Possible Solutions

Bypass Mode current unbalance condition

exceeded the unbalance level limit set by Z1-50 for

the amount of time specified in Z1-51.

• Check input wiring including fuses, breakers, connections, upstream from the bypass.
• Check the motor wiring and connections.

HOA Keypad Display

Fault Name

FB16

Input Phase Rotation

Cause

Possible Solution

Incorrect phase rotation while Z1-52 is set to 2 in

Bypass Mode.

Check the sequence (phase rotation) of the input wiring to the bypass package.

u

Modified Fault

HOA Keypad Display

Fault Name

CE

MEMOBUS/ Modbus Communication Error

Cause

Possible Solution

Communications between the bypass controller

and the drive have stopped for longer than 2

seconds.

Note:

Added in bypass controller software

version VST800298.

Check the communication cable, terminal CN6 on the bypass board, and terminals R+, R-, S+, and

S- on the drive terminal strip.

Note:

This fault may also occur when the bypass is initialized by setting Z1-01 to 1, 2, or 3.

Cycle power on the bypass to clear.

i.5 New and Modified Faults and Alarms

20

YASKAWA TOEP YAISUP 06A YASKAWA AC Drive – Z1000 Bypass Manual Supplement