9 troubleshooting – Yaskawa SI-W3 User Manual

Page 35

Advertising
background image

9 Troubleshooting

YASKAWA ELECTRIC TOBP C730600 56A 1000-Series Option SI-W3 Installation Guide

35

Digital Operator Display

Fault Name

EF0

External Fault Input from the option

The alarm function for an external device has been triggered.

Cause

Possible Solution

An external fault is being sent from the
network

• Remove the cause of the external fault
• Reset the external fault input from the network

Problem with the network program

Check the program used by the network and make the appropriate
corrections.

Digital Operator Display

Fault Name

oFA00

Non-Compatible Option connected to drive port CN5-A

Option is not properly connected.

Cause

Possible Solution

Non-compatible option connected to
drive port CN5-A

Use only compatible options. Connect the SI-W3 to CN5-A. For other
option connections refer to the Installation Manual for those options.

Digital Operator Display

Fault Name

oFA01

Option Fault (CN5-A)

Option is not properly connected.

Cause

Possible Solution

Problem with the connector between the
drive and option

Turn the power off and check the connectors between the drive and option.

Digital Operator Display

Fault Name

to

oFA30 to oFA43

Option Fault (CN5-A)

Communication ID error.

Cause

Possible Solution

Option hardware fault

Replace the option. Contact Yaskawa for assistance.

Digital Operator Display

Fault Name

oFb00

Non-Compatible Option connected to drive port CN5-B
Non-compatible option is connected.

Cause

Possible Solution

Non-compatible option connected to
drive port CN5-B

Use only compatible options. Connect the SI-W3 to CN5-A. For other
option connections refer to the Installation Manual for those options.

TOBP_C730600_56A_0_0_E.fm 35 ページ 2011年11月2日 水曜日 午後7時27分