7 Troubleshooting

YASKAWA ELECTRIC TOBP C730600 49A V1000 Option MECHATROLINK-II Installation Manual

25

LED Operator Display

Fault Name

E5

SI-T Watchdog Timer Error
The watchdog has timed out.

Cause

Possible Solution

Data has not been received from the
PLC, triggering the watchdog timer.

⇒ Execute DISCONNECT or ALM_CLR, then issue a CONNECT
command or SYNC_SET command and proceed to phase 3.

LED Operator Display

Fault Name

EF0

External Fault Input from MECHATROLINK-II Option
The alarm function for an external device has been triggered.

Cause

Possible Solution

An external fault is being sent from
the master controller (PLC).

⇒ Remove the cause of the external fault.

⇒ Reset the external fault input from the PLC device.

Problem with the PLC program

⇒ Check the program used by the PLC and make the appropriate
corrections.

LED Operator Display

Fault Name

oFA00

MECHATROLINK-II Option Fault
MECHATROLINK-II Option is not properly connected.

Cause

Possible Solution

Non-compatible option connected to
the drive

⇒ Connect an option that is compatible with the drive.

LED Operator Display

Fault Name

oFA01

MECHATROLINK-II Option Fault
MECHATROLINK-II Option is not properly connected.

Cause

Possible Solution

Problem with the connectors between
the drive and MECHATROLINK-II
Option

⇒ Turn the power off and check the connectors between the drive and
MECHATROLINK-II Option.