7 Troubleshooting

YASKAWA ELECTRIC TOBP C730600 49A V1000 Option MECHATROLINK-II Installation Manual

27

Minor Faults and Alarms

LED Operator Display

Minor Fault Name

AEr

Station Address Error
MECHATROLINK-II Option is set to an address outside the allowable
setting range.

Cause

Possible Solution

Minor Fault

(H2-†† = 10)

Address outside the specified address
range

⇒ Set F6-20 to an address within the specified range.

YES

LED Operator Display

Minor Fault Name

CALL

Serial Communication Transmission Error
Communication has not yet been established.

Cause

Possible Solution

Minor Fault

(H2-†† = 10)

Communication wiring is faulty, there
is a short circuit, or something is not
connected properly.

Check for wiring errors.

⇒ Correct the wiring.

⇒ Remove and ground shorts and reconnect loose
wires.

YES

Programming error on the master side

⇒ Check communications at start-up and correct
programming errors.

Communication circuitry is damaged.

Perform a self-diagnostics check.

⇒ Replace the drive if the fault continues to occur.