Troubleshooting Your Smart Trac DeviceNet Card Technical Manual 3554-0070

Look for patterns in the symptoms. Do intermittent problems occur
when other un-related equipment is in use?

Do some nodes communicate correctly? What is the difference
between the functioning nodes and the others (proximity to the
power supply, to the terminator, to the scanner)?. Is the device
improperly shielded or tied to ground at each device instead of at
ends?

Table 6. Hardware Configuration Troubleshooting.

Troubleshooting Hardware Configuration

Symptom

Probable
Cause

Corrective Action

Devices will
not
communicate

Baud rate
not same for
all devices

Check that baud rate is set correctly for
each device on the network.

MAC IDs not
unique for
each device
on network.

Check MAC Ids for all devices on the
network.

Faulty
devices

Opens or
shorts in the
network
wiring

Check for faulty connectors or cable.

Incorrect
Baud Rates
on some
devices

Check that baud rate is set correctly for
each device on the network.

Electrical
interference

Check for incorrect grounding or broken
shield.

Signal
distortion &
attenuation

Check for improper termination such as a
failure to adhere to topology guidelines,
or faulty connectors or loose terminal
blocks.

Missing
terminators

Excessive
common
mode
voltage

Check for excess current or cable length.

Check for faulty connectors.

Low power
supply
voltage

Check for excess current or cable length

Check for faulty connectors

Check that power supply is correctly
sized for number of devices in network

Excessive
signal
propagation
delay

Check for excess cable length.

Advertising