2 analog output object summary, 3 binary input object summary, 4 binary output object summary – Yaskawa GPD505 User Manual

Page 11: Nalog, Utput, Bject, Ummary, Inary, Nput

Advertising
background image

TM4028

7/12/2001

11

3.2 Analog Output Object Summary

Object

ID

Object Name

GPD505

Parameter

GPD506

Parameter

Units Default

Min

Max

AO1 Speed

Command n/a n/a

Note 1

0 0

Note 1

AO2 Acceleration

Time n019 n018

Sec

10.0 0 3600.0

AO3 Deceleration

Time n020 n019

Sec

10.0 0 3600.0

AO4

PID Proportional Gain

n086

n086

-

1.0

0.0

10.0

AO5

PID Integral Time

n087

n087

Sec

10.0

0.0

100.0

AO6

Stall Prevention Level – Run

n072

n074

%

Note 2

30 200

AO7

Stall Prevention Level –

Accel

n071 n073 %

Note 2

30 200

AO8

Operational Mode Select

n002

n002

-

3

0

8

AO9

PID Mode Select

n084

n084

-

0

0

3

AO10

Freq Command Upper Limit

n030

n031

%

100

0

109

AO11

Freq Command Lower Limit

n031

n032

%

0

0

100

AO12

Motor Rated Current

n032

n033

A

Note 2

Note 3

Note 3

AO13

First Prohibit Frequency

n058

n062

Hz

0.0

0.0

400.0

AO14

Second Prohibit Frequency

n059

n063

Hz

0.0

0.0

400.0

AO15

Prohibit Frequency BW

n060

n064

Hz

1.0

0.0

25.5

AO16

Number of Auto Restarts

n056

n060

-

0

0

10

AO17

Operator Display Mode

n024

n023

-

0

0

3999

AO18

Power Loss Ride-Through

n051

n055

-

0

0

2

AO19

Cable Loss Timeout

n/a

n/a

Sec

0

0

3600.0

AO20

Cable Loss Speed

n/a

n/a

Note 1

0 0

Note 1

AO21

Read Parameter Number

n/a

n/a

-

0

1

114

AO22

Write Parameter Number

n/a

n/a

-

0

1

114

AO23

Write Parameter Data

n/a

n/a

-

0

0

9999


Notes

1. Value dependent on setting of AO17, Operator Display Mode. Refer to Section 4.1.9.
2. Value dependent on drive capacity. Refer to appropriate Technical Manual.
3. Proper setting is between 10% and 120% of drive’s output current rating (AI14).

3.3 Binary Input Object Summary

Object

ID

Object Name

Default

Off (0)

State

On (1)

State

BI1 Run/Stop

Monitor 0

Stopped

Running

BI2 Forward/Reverse

Monitor 0

Forward

Reverse

BI3

Drive Ready Monitor

0

Not Ready

Ready

BI4

Fault Monitor

0

Not Faulted

Faulted

BI5

Drive Comm Error Monitor

0

No Error

Drive Comm Error

BI6

Multifunction Output 1

0

Note 1

Note 1

BI7

Multifunction Output 2

0

Note 1

Note 1

BI8

Safety Interlock Monitor

0

Safety Clear

(Term S1 closed)

Safety Set

(Term S1 open)


Notes

1. States are dependent on the setup of the Multifunction Outputs. Refer to appropriate Technical

Manual.

3.4 Binary Output Object Summary

Object

ID

Object Name

Default

Off (0)

State

On (1)

State

BO1 Run/Stop

Command

0

Stop

Run

BO2 Forward/Reverse

Command

0 Forward

Reverse

BO3

Serial Fault (EF0)

Command

0 No

Fault

Fault

Advertising
This manual is related to the following products: