4 operational mode – ao8, 5 speed command limits – ao10, ao11, 6 motor rated current – ao12 – Yaskawa GPD505 User Manual

Page 14: 4 operational mode – ao8 4.1.5, Speed command limits – ao10, ao11, 6 motor, Rated, Current – ao12

Advertising
background image

TM4028

7/12/2001

14

Object

ID

Object Name

GPD505

Parameter

GPD506

Parameter

Units Default

Min

Max

AO6

Stall Prevention Level – Run

n072

n074

%

Note 1

30 200

AO7

Stall Prevention Level –

Accel

n071 n073 %

Note 1

30 200


Notes

1. Value dependent on drive capacity. Refer to appropriate Technical Manual.

4.1.4 Operational Mode – AO8

This analog output defines the source for run and speed commands, as described below:

AO8 Run/Reverse

Command

Source

Speed Command

Source

Remarks

0

Digital Operator

Digital Operator

AO1, BO1, BO2 have no affect.

1

External Terminals

Digital Operator

AO1, BO1, BO2 have no affect.

2

Digital Operator

External Terminals

AO1, BO1, BO2 have no affect.

3

External Terminals

External Terminals

AO1, BO1, BO2 have no affect.

4

Digital Operator

Network

AO1 sets speed command.
BO1, BO2 have no affect

5

External Terminals

Network

AO1 sets speed command.
BO1, BO2 have no affect

6

Network

Network

AO1 sets speed command.
BO1 sets run command.
BO2 sets forward/reverse command.

7

Network

Digital Operator

AO1 has no affect.
BO1 sets run command.
BO2 sets forward/reverse command.

8

Network

External Terminals

AO1 has no affect.
BO1 sets run command.
BO2 sets forward/reverse command.



This object configures the drive as described below:

Object

ID

Object Name

GPD505

Parameter

GPD506

Parameter

Units Default

Min

Max

AO8

Operational Mode Select

n002

n002

-

3

0

8

4.1.5 Speed Command Limits – AO10, AO11

These analog outputs define the upper and lower speed command limits. Each value is specified as a
percentage of the maximum drive output frequency, defined by GPD505 parameter n012 or GPD506
parameter n011. These objects configure the drive as described below:

Object

ID

Object Name

GPD505

Parameter

GPD506

Parameter

Units Default

Min

Max

AO10

Freq Command Upper Limit

n030

n031

%

100

0

109

AO11

Freq Command Lower Limit

n031

n032

%

0

0

100

4.1.6 Motor Rated Current – AO12

This analog output defines the current rating of the motor, configuring the drive as described below: