Connecting the valve wiring, Figure 6, Installation procedures – Irritrol Total Control-R Series User Manual

Page 23

Advertising
background image

21

CONNECTING THE VALVE WIRING

1. To provide a field common wire, attach one wire to either solenoid

lead of all sprinkler valves and master valve (optional).

2. Attach a separate control wire to the remaining solenoid lead of

each valve. Label the control wires with the intended station
number for identification at the controller.

Caution: All wiring splices must be waterproofed to prevent short
circuits and corrosion.
Caution: A maximum load of 12 VA (0.5 amps) may be connected
to each station. A maximum load (including master valve) of 30 VA
(1.25 amps) may be programmed to operate simultaneously.
Exceeding these limits can damage the controller.

3. Route the control and common wires into the controller cabinet

through the bottom access opening. Remove approximately
1/2" (13mm) insulation from the ends of each wire.

4. Attach the field common wire to one of the three valve common

terminals labeled “VC.”

5. Referring to Figure 6 connect each valve control wire to the

appropriate station number terminal. If an optional master valve is
installed, connect its control wire to the terminal labeled “MV.”
Tighten all terminal screws securely.

Installation Procedures

ACTIVE

24V

EARTH

GND

AC

G

N

D

BYPASS

SENSOR

SENSOR

VALVE
TEST

Pump Start

Relay

or

Master Valve

Field Common

Figure 6

Valve

Sta. 3

Valve

Station 2

Valve

Station 1

Advertising
This manual is related to the following products: