To Use the Vent Graph (Figure 29)

1. Determine the height of the center of the

horizontal vent pipe. Using this dimension on

the Sidewall Vent Graph, locate the point it

intersects with the slanted graph line.

2. From the point of this intersection, draw a vertical

line to the bottom of the graph.

3. Select the indicated dimension, and position the

unit in accordance with same.

EXAMPLE A:

If the vertical dimension from the floor of the unit

is 12 feet, 4 inches the horizontal run to the outer

wall flange must not exceed 12 feet, 3 inches.
EXAMPLE B:

If the vertical dimension from the floor of the unit

is 6 feet, 9 inches, the horizontal run to the outer

wall flange must not exceed 6 feet, 6 inches.
SPECIAL NOTE: For each 45 degree elbow

installed in the horizontal run, the length of the

horizontal run MUST be reduced by 18" (45cm).

This does not apply if the 45 degree elbows are

installed on the vertical part of the vent system.

Reduce 3' for every 90° elbow.
Example: According to the chart the maximum

horizontal vent length is 20' and if two 45 degree

elbows are required in the horizontal vent it must

be reduced to 17'.
The maximum number of 45 degree elbows

permitted per side wall installation is two (2).

These elbows can be installed in either the vertical

or horizontal run.

Figure 29

Acceptable vertical and horizontal vent run.
Unacceptable vertical and horizontal vent run.

Note: When rear venting unit, adjust air shutter from 1/16" open

up to between 1/8" and 3/16" for NAT gas.
Adjust air shutter from 1/4" open to between 5/16" and 3/8" for

LP gas.

Venting Graph (Dimensions in Feet)

Note: When rear venting unit, adjust air shutter

from 1/16" open up to between 1/8" and 3/16"

for NAT gas.
Adjust air shutter from 1/4" open to between 5/16"

and to 3/8" for LP gas.

VERTICAL

DIMENSION

FROM

THE

BOTT

OM

OF

THE

UNIT

TO

THE

CENTER

OF

THE

FLUE

OUTLET

WITH

VERTICAL

OR

HORIZONT

AL

TERMINA

TION

CAPS

26

27

28

29

30

31

32

33

34

35

36

37

38

39

40

HORIZONTAL RUN

REAR EXIT - VERTICAL AND HORIZONTAL TERMINATION

(DIMENSIONS IN FEET)

REAR HORIZONTAL

VENT CONNECTION

B

A

DVD48FP(ONLY)

VENTING FIREPLACE - REAR