Framing and finishing – Empire Comfort Systems DVD36FP3 EN User Manual

Page 24

Advertising
background image

23552-1-0607

Page 24

Installing Support Brackets (Figure 37)

A horizontal pipe support MUST BE used for each 3 feet of horizontal

run. The pipe supports should be placed around the pipe and nailed

in place to framing members. There MUST BE a 3 inch clearance

to combustibles above 6 5/8 inch diameter pipe and elbows and

1 inch clearance on both sides and bottom of 6 5/8 inch pipe to

combustibles on all horizontal pipe sections and elbows.
Vertical runs of this vent systems must be supported every 4 feet

above the appliance flue outlet by wall brackets attached to the 6

5/8 inch vent pipe and secured with nails or screws to structural

framing members.

Figure 37

Installing Firestops (Figures 38, 39, 40 and 41)

Firestops are required for safety whenever the vent system passes

through an interior wall, an exterior wall, or a ceiling. These firestops

act as a firebreak heat shield and as a means to insure that minimum

clearances are maintained to the vent system.
Horizontal runs in the vent system which pass through either interior

or exterior walls, require the use of wall firestops on both sides of

the wall through which the vent passes.
Position the firestops on both sides of the 10 inch x 10 inch hole,

previously cut. Secure with nails or screws. The heat shields of the

firestops MUST BE placed towards the top of the hole. Continue

the vent run through the firestops. (See Figure 38)

10”

11”

Figure 38

Vertical runs of this system which pass through ceilings require the

use of ONE (1) ceiling firestop at the hole in each ceiling through

which the vent passes.
Position a plumb bob directly over the center of the vertical vent

component and mark the ceiling to establish the center point of the

vent. Drill a hole or drive a nail through this center point and check

the floor above for any obstructions such as wiring or plumbing

runs. Reposition the appliance and vent system, if necessary, to

accommodate ceiling joists and/or obstructions.
Cut a 10 inch x 10 inch hole through the ceiling, using the center

point previously marked. Frame the hole with framing lumber the

same size as the ceiling joists. (See Figure 39) If the area above

the ceiling is NOT an attic, position and secure the ceiling firestop

(SD-963) on the ceiling side of the previously cut and framed hole.

(See Figure 40) If the area above the ceiling is an attic, position

and secure the firestop on top of the previously framed hole. (See

Figure 41)
NOTE: Remove insulation from the framed area in the attic before

installing the firestop and/or vent pipes.

FRAMING AND FINISHING

Advertising