REQUIREMENTS FOR MASSACHUSETTS

For all side wall horizontally vented gas fueled equipment

installed in every dwelling, building or structure used in

whole or in part for residential purposes, including those

owned or operated by the Commonwealth and where the

side wall exhaust vent termination is less than seven (7) feet

above finished grade in the area of the venting, including but

not limited to decks and porches, the following requirements

shall be satisfied:

1. INSTALLATION OF CARBON MONOXIDE

DETECTORS. At the time of installation of the side wall

horizontal vented gas fueled equipment, the installing

plumber or gasfitter shall observe that a hard wired

carbon monoxide detector with an alarm and battery

back-up is installed on the floor level where the gas

equipment is to be installed. In addition, the installing

plumber or gasfitter shall observe that a battery operated

or hard wired carbon monoxide detector with an alarm

is installed on each additional level of the dwelling,

building or structure served by the side wall horizontal

vented gas fueled equipment. It shall be the responsibility

of the property owner to secure the services of qualified

licensed professionals for the installation of hard wired

carbon monoxide detectors

a. In the event that the side wall horizontally vented

gas fueled equipment is installed in a crawl space or

an attic, the hard wired carbon monoxide detector

with alarm and battery back-up may be installed on

the next adjacent floor level.

b. In the event that the requirements of this subdivision

can not be met at the time of completion of

installation, the owner shall have a period of thirty

(30) days to comply with the above requirements;

provided, however, that during said thirty (30) day

period, a battery operated carbon monoxide detector

with an alarm shall be installed.

2. APPROVED CARBON MONOXIDE DETECTORS.

Each carbon monoxide detector as required in accordance

with the above provisions shall comply with NFPA 720

and be ANSI/UL 2034 listed and IAS certified.

3. SIGNAGE. A metal or plastic identification plate shall be

permanently mounted to the exterior of the building at a

minimum height of eight (8) feet above grade directly in

line with the exhaust vent terminal for the horizontally

vented gas fueled heating appliance or equipment. The

sign shall read, in print size no less than one-half (1/2)

inch in size, “GAS VENT DIRECTLY BELOW.

KEEP CLEAR OF ALL OBSTRUCTIONS”.

4. INSPECTION. The state or local gas inspector of the

side wall horizontally vented gas fueled equipment shall

not approve the installation unless, upon inspection,

the inspector observes carbon monoxide detectors and

signage installed in accordance with the provisions of

248 CMR 5.08(2)(a) 1 through 4.

(b) EXEMPTIONS: The following equipment is

exempt from 248 CMR 5.08(2)(a)1 through 4:

1. The equipment listed in Chapter 10 entitled

“Equipment Not Required To Be Vented” in the

most current edition of NFPA 54 as adopted by

the Board; and

2. Product Approved side wall horizontally vented

gas fueled equipment installed in a room or

structure separate from the dwelling, building or

structure used in whole or in part for residential

purposes.

(d) MANUFACTURER REQUIREMENTS - GAS

EQUIPMENT VENTING SYSTEM NOT

PROVIDED. When the manufacturer of a Product

Approved side wall horizontally vented gas fueled

equipment does not provide the parts for venting the

flue gases, but identifies “special venting systems”,

the following requirements shall be satisfied by the

manufacturer:

1. The referenced “special venting system”

instructions shall be included with the appliance

or equipment installation instructions; and

2. The “special venting systems” shall be Product

Approved by the Board, and the instructions for

that system shall include a parts list and detailed

installation instruction.

(e) A copy of all installation instructions for all Product

Approved side wall horizontally vented gas fueled

equipment, all venting instructions, all parts lists

for venting instructions, and/or all venting design

instructions shall remain with the appliance or

equipment at the completion of the installation.