Eagle Instruction Manual

Appendix H: Eagle Transformer Gas Tester Model • 78

NOTE:

The Eagle can be calibrated either with or without the dilution
fitting in place. If calibrated without the dilution fitting in
place, then display readings must be doubled to determine
the actual gas concentration. If calibrated with the dilution
fitting in place, then the sample bag must be used during
calibration, and the display readings will be the actual gas
concentrations.

CAUTION:

If the dilution fitting is in place for calibration, do not use a
demand flow regulator. Use a sample bag. The use of a demand
flow regulator with a dilution fitting when calibrating will
result in an inaccurate calibration.

Alarms

All the gas alarms on the Transformer Gas Tester are set to OFF.

Part List

Table 17: Parts List: Eagle Tank Tester Model

Part Number

Description

80-0405RK

Dilution fitting (1:1)

81-1126RK

Sample bag, 9” x 9”, tedlar