Programming the meter ( prog ) – Precision Digital PD6830 User Manual

Page 29

Advertising
background image

PD6830 Pulse Input Rate/Totalizer Instruction

Manual

29

Programming the Meter (PRoG)

It is very important to read the following information, before proceeding to program
the meter:
 There

is

no need to recalibrate the meter for frequency in Hz when first

received from the factory.

The meter is factory calibrated for Hz prior to shipment. The calibration
equipment is certified to NIST standards.

 Use

the

Factor menu to enter a K-Factor - or

 Use

the

Scale menu to enter the default 2-point scaling without a signal source - or

 Use

the

Calibrate menu to apply a signal from a calibrator or a flowmeter for the

default 2-point scaling.

Note: The K-Factor, Scale, and Calibrate functions are exclusive of each other.
The meter uses the last function programmed. Only one of these methods can
be employed at a time. The Scale and Calibrate functions can use up to 32
points (default is 2). The number of points should be set in the Advanced menu
under the
Multi-Point Linearization (LINEAR) menu selection prior to scaling and
calibration of the meter, see page 44 for details.

Additional parameters, not needed for most applications, are viewed and
programmed in the Advanced menu. See Advanced Features Menu page 40.

Advertising