Reset, Rate, Total – Precision Digital PD6830 User Manual

Page 42

Advertising
background image

PD6830 Pulse Input Rate/Totalizer Instruction

Manual

42

For instructions on how to program numeric values
see Setting Numeric Values, page 26.

Indication (INDICAT)

The Indication menu is used to enable and set up a high or low rate alarm or total set
point alarm indication on the screen. When in alarm condition, a HI, LO, or SET
symbol is displayed accompanied by a flashing display until the ACK is pressed or
the condition is cleared (reset).

Rate high alarm trip point: program set point above reset point.

Rate low alarm trip point: program set point below reset point.

Rate alarm deadband is determined by the difference between set and reset
points. Minimum deadband is one display count. If set and reset points are pro-
grammed the same, output will reset one count below set point.

Total alarm trip point: program total set point. Alarm reset is triggered by total
reset (There is no reset parameter entered for total). If automatic total reset is
enabled, this setting will be the trigger point for the timer.

INDICAT

ALRNm

INDICAT

off

INDICAT

Accept

Setting

set

RATE

Enter

Set Point

1

000.0

SET

reset

RATE

Enter Reset Point

0

500.0

RESET

rate

ALARM

total

ALARM

set

TOTAL

SET

0

01000.0

Enter Set Point

To acknowledge alarm, press the ENTER/ACK button once for acknowledge
prompt and a second time to confirm.

Advertising