PD6830 Pulse Input Rate/Totalizer Instruction

Manual

6

SPECIFICATIONS

Except where noted all specifications apply to operation at +25°C.

General

DISPLAY

Five digits rate
(-9999 to 99999)

0.7" (17.8 mm) high, 7-segment,
automatic lead zero blanking.

Seven characters
Total and/or Tag

0.4" (10.2 mm) high, 14 segment,
automatic lead zero blanking.

Symbols

High, Low, & Set Alarm, Password Lock

DISPLAY
UPDATE RATE

Ambient > -25°C: 1 Updates/Second
Ambient < -25°C: 1 Update/5 Seconds
Note: Update is dependent on gate settings.

OVERRANGE

Display flashes

99999

BACKLIGHT

White LED, 10 sec auto-off for battery powered models.

PROGRAMMING
METHODS

Four SafeTouch

®

through-glass buttons when cover is

installed. Four internal pushbuttons when cover is removed.

RECALIBRATION

All ranges are calibrated at the factory to read frequency in
Hz. No recalibration required.

MAX/MIN
DISPLAY

Max/Min readings reached by the process are stored until
reset by the user or until power to the meter is cycled.

PASSWORD

Programmable password restricts modification of programmed
settings and manual total reset via button interface.

NON-VOLATILE
MEMORY

All programmed settings and total reading are stored in non-
volatile memory for a minimum of ten years if power is lost.

POWER OPTIONS

9-30 VDC, 2.2 W max

4-20 mA Transmitter Output Power, 30 VDC max

Battery Power

DC Power with battery backup

BATTERY

3.6 V Primary Lithium (Li-SOCl

2

), non-rechargeable

Expected Service Life:

5 Years

Recommended
Replacement Interval:

3 Years when exclusive source
10 Years in backup configuration

Model PDABAT36D

ISOLATION

All Models:

500 V opto-isolated input-to-power/output

PD6830-BTA: 500 V input-to-output

PD6830-APA: 500 V input/power-to-output

Note: Requires separate output supply

Advertising