REQUIREMENTS FOR MASSACHUSETTS

For all side wall horizontally vented gas fueled equipment installed

in every dwelling, building or structure used in whole or in part

for residential purposes, including those owned or operated by the

Commonwealth and where the side wall exhaust vent termination

is less than seven (7) feet above finished grade in the area of the

venting, including but not limited to decks and porches, the fol-

lowing requirements shall be satisfied:

1. INSTALLATION OF CARBON MONOXIDE DETECTORS.

At the time of installation of the side wall horizontal vented

gas fueled equipment, the installing plumber or gasfitter shall

observe that a hard wired carbon monoxide detector with an

alarm and battery back-up is installed on the floor level where

the gas equipment is to be installed. In addition, the installing

plumber or gasfitter shall observe that a battery operated or

hard wired carbon monoxide detector with an alarm is installed

on each additional level of the dwelling, building or structure

served by the side wall horizontal vented gas fueled equipment.

It shall be the responsibility of the property owner to secure the

services of qualified licensed professionals for the installation

of hard wired carbon monoxide detectors.

(a) In the event that the side wall horizontally vented gas

fueled equipment is installed in a crawl space or an attic,

the hard wired carbon monoxide detector with alarm and

battery back-up may be installed on the next adjacent floor

level.

(b) In the event that the requirements of this subdivision can

not be met at the time of completion of installation, the

owner shall have a period of thirty (30) days to comply

with the above requirements; provided, however, that dur-

ing said thirty (30) day period, a battery operated carbon

monoxide detector with an alarm shall be installed.

2. APPROVED CARBON MONOXIDE DETECTORS. Each

carbon monoxide detector as required in accordance with the

above provisions shall comply with NFPA 720 and be ANSI/UL

2034 listed and IAS certified.

3. SIGNAGE. A metal or plastic identification plate shall be per-

manently mounted to the exterior of the building at a minimum

height of eight (8) feet above grade directly in line with the

exhaust vent terminal for the horizontally vented gas fueled

heating appliance or equipment. The sign shall read, in print

size no less than one-half (1/2) inch in size, “GAS VENT

DIRECTLY BELOW. KEEP CLEAR OF ALL OBSTRUC-

TIONS”.

4. INSPECTION. The state or local gas inspector of the side wall

horizontally vented gas fueled equipment shall not approve

the installation unless, upon inspection, the inspector observes

carbon monoxide detectors and signage installed in accordance

with the provisions of 248 CMR 5.08(2)(a) 1 through 4.

(b) EXEMPTIONS: The following equipment is exempt from

248 CMR 5.08(2)(a)1 through 4:

1. The equipment listed in Chapter 10 entitled “Equip-

ment Not Required To Be Vented” in the most current

edition of NFPA 54 as adopted by the Board; and

2. Product Approved side wall horizontally vented gas

fueled equipment installed in a room or structure

separate from the dwelling, building or structure used

in whole or in part for residential purposes.

(c) MANUFACTURER REQUIREMENTS - GAS EQUIP-

MENT VENTING SYSTEM PROVIDED. When the

manufacturer of Product Approved side wall horizontally

vented gas equipment provides a venting system design

or venting system components with the equipment, the

instructions provided by the manufacturer for installation

of the equipment and the venting system shall include:

1. Detailed instructions for the installation of the vent-

ing system design or the venting system components;

and

2. A complete parts list for the venting system design

or venting system.

(e) A copy of all installation instructions for all Product Ap-

proved side wall horizontally vented gas fueled equipment,

all venting instructions, all parts lists for venting instruc-

tions, and/or all venting design instructions shall remain

with the appliance or equipment at the completion of the

installation.