EN - 24

6.1.3. "HARM" mode
Selecting the HARM mode one of the below screens will be displayed according to the
settings made as per paragraph 5.2. The screens show the harmonics (see paragraph
16.2) of the phase or phase-to-phase voltage.


Example of screen in single-

phase system

Example of screen in “3 wires”

three-phase system

Example of screen in “4 wires”

three-phase system

The symbols used are described in Tab. 1. For eventual messages displayed see
Appendix 1

– MESSAGES DISPLAYED. The displayed histograms represent the harmonic

content of the voltage under test. The value of the first harmonic h01 (fundamental at
60Hz) is not represented in scale along with the other harmonics in order to maximize the
display of the latter. In case both voltage and current are connected to the instrument
inputs, eventual negative values of the harmonics (therefore represented under the
horizontal axis), indicate that such voltage harmonics are “generated” by the load.
Following keys are enabled:

F3, F4:

to move the cursor of the selected harmonic leftwards and rightwards
respectively. At the same time the values relevant to the order no. of
the selected harmonic and to the corresponding absolute and relative
values (calculated on the basis of the fundamental) are updated.

F1

(only for three-phase mode): to display the values of the harmonics of
the other voltages available. The voltage displayed is indicated above
the F3 key.

F2:

to display the page of the harmonics h01

h24 (symbol h24) or that of

the harmonics h25

h49 (symbol h49).

ESC:

to return back to METER mode (see paragraph 6.1.2).

SAVE:

to save in the instrument memory a “Smp” type record (see paragraph
5.4) and the instantaneous values of voltage and current present on the
instrument inputs. This function is disabled during a recording.

ENTER/HOLD: to enable/disable the HOLD function (updating interruption) of the

displayed data. All the previous functions remain however available.
When the HOLD function is enabled, the word

HOLD

is displayed.

When this function is enabled it’s not possible to record or take an
energy measurement. This function is disabled during a recording or an
energy measurement.

MENU:

to enter in the MENU mode and change the instrument settings (see
paragraph 5.2 and 5.3

). It’s not possible to enter the configuration

MENU during a recording or an energy measurement.

START/STOP: to record selected parameters

according to the instrument’s settings

(see chapter 7).

27.09.00 17:35:12

V1 = 230.2 V

h03 = 10.2 V

h03 = 4.3 %

ThdV = 11.0 %

h49

27.09.00 17:35:12

V12 = 400.2 V

h03 = 14.2 V

h03 = 3.5 %

ThdV = 11.0 %

ChgP

h49

27.09.00 17:35:12

V1 = 230.2 V

h03 = 10.2 V

h03 = 4.3 %

ThdV = 11.0 %

ChgP

h49