Amprobe BAT-500 Battery-Impedance-Tester User Manual

Page 13

Advertising
background image

6

6. Press u key one time, the high limit impedance of the “two higher

digits” will be flashing. (Use the p & q keys to select the desired value.)

7. Press u key one time, the high limit impedance of the “two lower

digits” will be flashing. (Use the p & q keys to select the desired value.)

8. Press u key one time, the throughold voltage of the “tow higher digits”

will be flashing. (Use the p & q keys to select the desired value.)

9. Press u key one time, the throughold voltage of the “two lower digits”

will be flashing. (Use the p & q keys to select the desired value.)

10. Repeat step 2 to step 9 to set the next comparator number.

11. Press SET key again to exit from comparator setting mode.

Comparator Tables

Impedance

Voltage

Low limit impedance High limit impedance

Voltage Lo

Comparison

Value Hi

WARNING

Beeper

WARNING

Beeper

FAIL

Beeper

Pass

WARNING

Beeper

FAIL

Beeper

Start / Stop Controls the Comparator

1. Press SET key to start comparator function, the COMP indication will

appear on the display, and the comparator will be operating once the
measurements are taken.

2. Press p and q keys to select the desired comparator number. The

selected comparator number remains in memory even the power is
turned off.

3. Press

R

key to set the beeper on, the

indication will appear on the

display, and the beeper will sound when getting the WARNING or FAIL
result. Press

R

key again to set the beeper off.

4. Press SET key again to stop comparator function.

Lo

Middle

Hi