Amprobe BAT-500 Battery-Impedance-Tester User Manual

Page 17

Advertising
background image

10

Electrical Specifications

Conditions to guarantee accuracy

Temperature : 23

°C

± 5

°C (73.4

°F ±41°F)

Humidity : 80%RH or less (no condensation).

Zero adjustment : After zero adjustment for each range.

Impedance measurement

Temperature coefficient : (±0.1% rdg ± 0.5dgs) /

°C

Measuring current frequency : 1KHz ± 10%
Measuring burden voltage : 1.5mVAC

Range

Resolution

Measurement current

Accuracy

40mΩ

10µΩ

25mA approx

±(1% reading ±

10 digits)

400mΩ

100µΩ

2.5mA approx

4Ω

1mΩ

250µA approx

40Ω

10mΩ

25µA approx

Voltage Measurement
Temperature coefficient (±0.1%rdg±0.5dgts)/

°C

Range

Resolution

Accuracy

4V

1mV

±(0.1% reading ± 6digits)

40V

10mV

Maximum Input Voltage : 50VDC maximum, No AC voltage input, Between

input terminals and ground, 60VDC and AC maximum.

�

DANGER!

Do not exceed the maximum permissible input voltage to the measurement
terminal. This could result in injury or damage to the unit.