Electrical Specifications

Conditions to guarantee accuracy

Temperature : 23

°C

± 5

°C (73.4

°F ±41°F)

Humidity : 80%RH or less (no condensation).

Zero adjustment : After zero adjustment for each range.

Impedance measurement

Temperature coefficient : (±0.1% rdg ± 0.5dgs) /

°C

Measuring current frequency : 1KHz ± 10%
Measuring burden voltage : 1.5mVAC

Range

Resolution

Measurement current

Accuracy

40mΩ

10µΩ

25mA approx

±(1% reading ±

10 digits)

400mΩ

100µΩ

2.5mA approx

1mΩ

250µA approx

40Ω

10mΩ

25µA approx

Voltage Measurement
Temperature coefficient (±0.1%rdg±0.5dgts)/

°C

Range

Resolution

Accuracy

4V

1mV

±(0.1% reading ± 6digits)

40V

10mV

Maximum Input Voltage : 50VDC maximum, No AC voltage input, Between

input terminals and ground, 60VDC and AC maximum.

DANGER!

Do not exceed the maximum permissible input voltage to the measurement
terminal. This could result in injury or damage to the unit.