Amprobe BAT-500 Battery-Impedance-Tester User Manual

Page 15

Advertising
background image

8

SPECIFICATIONS
General Specifications

Measuring method : Impedance (AC four-terminal method).

A/D conversion : Dual slope method.

Display : Dual display LCD and LEDs (comparator output).

Sampling rate : 1 set (impedance and voltage measurements) / second.
Open-Circuit terminal voltage : 3.5Vpp max.

Input over range : “OL” display.
Low battery detection “ ” display.
Test current fault detection : “- - - - ” display.

Auto power off : Power off automatically after about 30 minutes.

Zero adjustment function : Circuit offset voltage is displayed as 0V.

Hold function : Display is held.

Beeper function : Audible output for warning and fail results (can be turned
on and off).

Comparator settings : Impedance High and Low limits and voltage throughold
point.

Number of comparator settings : 99 sets.

Comparator output : LEDs for pass (green), warning (yellow) and fail (red)
results audible tone for warning and fail results.

Impedance

Voltage

Lo

IN

Hi

Lo

Warning

Warning

Fail

Hi

Pass

Warning

Fail

Manual Data logging : 500 sets.

Continuous Data logging : 9600 sets.

Operating environment : 0

°C

~ 40

°C

(32

°F

~ 104

°F)

80%RH (no condensation)

Storage environment : -10

°C

~ 50

°C

(14

°F ~ 122°F)

80%RH (no condensation)

Power source: 6 AA size 1.5V batteries. (AC adaptor (output 9VDC) is optional)

Maximum power consumption : 1.0VA

Continuous operating time : 7 hours approx.