Amprobe ACD-45PQ Power-Quality-Clamp User Manual

Page 17

Advertising
background image

11

• After the kWHr Recording session is stopped (“

”) properly, the new

result will supersede the previous one stored in the non-volatile memory.
You can then switch off the meter for transportation, storage, or even
battery changing with memory remained.

• To avoid mis-storage to memory, it is important to properly stop (“

”)

kWHr Recording session before sliding the slide-switch function-selector
to any other function positions.

3-Phase 3-Wire (3

3W) Unbalanced-Load Power Function

• Set the slide-switch function-selector to the “3~Un-Bal” Power position.

Press “3W4W” button momentarily to select 3-Wire measurements.
Annunciator “3W” turns on.

• Clamp the jaws around “Line 1” as reminded by annunciators “ L1”,

and connect Black test probe (COM terminal) to “Line 3” and Red test
probe (+ terminal) to “Line 1” as reminded by annunciators “

” on

mini-display.

• When the reading is stable, press “

” button momentarily to enter the

first measuring value.

• Then clamp the jaws around “Line 2” as reminded by annunciators “

L2”, and connect Black test probe (COM terminal) to “Line 3” and Red
test probe (+ terminal) to “Line 2” as reminded by annunciators “

” on mini-display.

• When the reading is stable, press “

” button momentarily to enter the

second measuring value. The meter will then calculate, store and display
the total 3-Phase Power result automatically. Annunciators “ L1 L2 L3”
turn on.

• Press “

” button momentarily again for new measurements.

• Press “SELECT” button momentarily to view (“

”) the last stored

result. Annunciator “

” turns on & flashes. Press “SELECT” button

momentarily again to continue (“

”).