Dm-ii, Data logger/recorder – Amprobe DMII-PRO Data-Logger-Recorder User Manual

Page 32

Advertising
background image

M

ODEL

DM-II™

Data Logger/Recorder

Specifications

Inputs:

Voltage: Three voltage channels with common (V1, V2, V3, and COM). The test leads are flexi-

ble

straight sheathed banana plugs on each end, rated for 1000Vrms and a length of 6 Ft.
(set of four supplied). The alligator clips have a 1 in. jaw opening and are rated at 10A max.
(set of four supplied).

Current: Four channels (

I1, I2, I3, I4

)

DM-CT: 1 to 1000A ±1% of reading (four supplied)
ACF-3000:

30A to 300A ±1% of full scale
300A to 3000A ±1% of full scale

Note: The ACF-3000 is an optional accessory. A total of three would be
required for a 3Ø measurement.

Ranges:

AC Voltage measurements (True RMS) 5 to 600 Vrms
AC Current measurements (True RMS) 1 to 1000 Arms with four supplied DM-CTs

Accuracy:

Voltage measurements ±1% of reading + 3 LSDs
Current measurements ±1% of reading + 3 LSDs

Voltage and Current measurement selections:

True RMS voltage and current, RMS max, RMS min, RMS avg, Peak max

Power measurement capabilities:

Real power P (watts), Apparent Volt-amperes S (VA),
Reactive Volt-amperes Q (VAR), True Power Factor (tPF),

Energy measurement capabilities:

Kilowatt Hours (KWH), Demand (KW)

Programmable Thresholds:

User selectable high/low limits for RMS voltage and current

Recording Modes/Rates/Intervals:

User selectable normal and loop (wrap around) recording modes, user selectable
recording rates of 1 second, 5 seconds, 15 seconds, 30 seconds, 1 minute, 5 minutes,
15 minutes, and 30 minutes. User selectable recording intervals of none, 15 minutes,
and 30 minutes.