CT Set-up

Check if the type of CT’s you are using matches the set-up on the DM-II PRO.

To set up the ACF-3000 itself, please refer to the ACF-3000 DM manual.

To change a CT set-up on the DM-II

Step 1 - Simply highlight CT in Setup screen using up/down arrows on the keypad and press

ENTER

(red square).

Step 2 - Using same arrow keys, highlight desired CT.

Step 3 - Press

ENTER

again.

PROPER SET-UP

TYPE OF CURRENT TRANSDUCERS

RANGE

OF THE DM-II

DM-CT or

Standard CTs

0-1000 amps

CT

DM-CT

DM-CT CE

shipped with every DM-II PRO

ACF-3000DM

Optional flexible CTs set-up

30-300 amps

CT

ACF3000 300

ACF-3000 DM

Optional flexible CTs

300-3000 amps

CT

ACF3000 3000

Page 8