Commissioning

WARNING

• Measurements in dangerous proximity of electrical installations are only to be executed

when instructed by a responsible electrical specialist, and never alone.

• To perform this measurement the user requires the Earth Measurement Set (option).

• The instrument may only be connected to voltage-free earth connectors.

• Prior to inserting grounds or rods, check the soil for possible dangerous objects present

(pipes, conductors, etc.).

• If a voltage exceeding approx. 5V AC/DC is present at the test leads, the warning message

'Unoise' is displayed.

• To avoid faulty measurements, installed metal pipes, cables in the ground, or in open area

underground waterways or roots must be taken into account. Additionally, the specific
ground resistance is subject to seasonal weather-related variations.