Introduction/ Contents

You have purchased a high quality measurement instrument of BEHA-AMPROBE GmbH which
will allow you to carry out measurement over a long time period.
The Amprobe EARTH-TEST is a handy test and measurement instrument for testing
Earthresistance. The Amprobe EARTH-TEST is characterised by the following features:

Determination of earth resistance or specific earth resistance
2, 3, and 4-wire measurements possible
Measurement of specific earth resistance measurement in compliance with the Wenner

method

Measurement current of approx. 10mA
Display and monitoring of both auxiliary earth and probe resistances
Displays the actual test current to further enhance and control measurement quality
Probe and auxiliary ground resistance up to 50 k

Ω

Noise voltage detection
Two measurement frequencies for noise voltage suppression
Automatically optimised measurement frequency selection
Pre-selection of maximum admissible contact voltage: VL 25 or 50 V
Large, visible LC-display
Energy management
Built in accordance with EN61557-5, IEC61557-5

Contents:

1 pc EARTH-TEST
1 pc test lead, black
1 pc test lead, blue
1 pc crocodile clamps, black
1 pc crocodile clamps, blue
1 pc carrying holster
6 pc batteries 1.5V Mignon Type IEC LR6 (Size AA)
1 pc instruction manual

Transport and Storage

• Please keep the original packaging for later transport, e.g. for calibration. Any transport

damage due to faulty packaging will be excluded from warranty claims.

• In order to avoid instrument damage, it is advised to remove batteries when not using the

instrument over a certain time period. However, should the instrument be contaminated
by leaking battery cells, you are kindly requested to return it to the factory for cleaning and
inspection.

• Instruments must be stored in dry and closed areas. In the case of an instrument being

transported in extreme temperatures, a recovery time of at least 2 hours is required prior
to instrument operation.