ProSoft Technology MVI69-ADM User Manual

Page 171

Advertising
background image

MVI-ADM ♦ 'C' Programmable

Application Development Function Library - ADM API

'C' Programmable Application Development Module

Developer's Guide

ProSoft Technology, Inc.

Page 171 of 342

February 20, 2013

ADM_BtNext

Syntax

int ADM_BtNext(ADMHANDLE adm_handle, ADM_INTERFACE * adm_interface_ptr)

Parameters

adm_handle

Handle returned by previous call to ADM_Open

adm_interface_ptr

Pointer to ADM_INTERFACE structure to allow API access to
structures

Description
This function sets the next write block number.

MVI56 Note
If the write block is equal to the maximum write block, the next write block will be
set to 1. If the maximum is 1, the next write block will be 0. If the maximum is 0,
then the next write block will be -1.

MVI94 Note
If the write block is equal to the maximum write block, the next write block will be
set to 1.

MVI69 Note
If the write block is equal to the maximum write block, the next write block will be
set to 0. If the maximum is 0, the next write block will be -1.

MVI46 Note
This is a null function for the MVI46.

Return Value

ADM_SUCCESS

No errors were encountered

ADM_ERR_NOACCESS

adm_handle does not have access

ADM_ERR_NOTSUPPORTED

Function is not supported on this platform

Example

ADMHANDLE adm_handle;
ADM_INTERFACE *interface_ptr;
ADM_INTERFACE interface;
interface_ptr = &interface;
ADM_BtNext(adm_handle, interface_ptr);

See Also
ADM_BtOpen (page 169)

Advertising