MVI-ADM ♦ 'C' Programmable

Understanding the MVI-ADM API

'C' Programmable Application Development Module

Developer's Guide

ProSoft Technology, Inc.

Page 31 of 342

February 20, 2013

All data used by the module is stored in its internal database. The following
illustration shows the layout of the database:

User data contained in this database is continuously read from the M1 file. The
configuration data is only updated in the M1 file after each configuration request
by the module to the SLC. All data in the M1 file is available to devices on the
foreign networks. This permits data to be transferred from these devices to the
SLC using the user data area. Additionally, remote devices can alter the
module's configuration, read the status data and issue control commands. Block
identification codes define specific functions to the module.

The block identification codes used by the module are listed below:

Block Range

Descriptions

9000

Configuration request from module

9001

Configuration ready from controller

9997

Write configuration to controller

9998

Warm-boot control block

9999

Cold-boot control block

Each block has a defined structure depending on the data content and the
function of the data transfer as defined in the following topics.

Normal Data Transfer
This version of the module provides for direct access to the data in the module.
All data related to the module is stored in the module’s M1 file. To read data from
the module, use the COP instruction to copy data from the module’s M1 file to a
user data file. To write data to the module, use the COP instruction to copy data
from a user file to the module’s M1 file. Registers 0 to 4999 should be used for
user data. All other registers are reserved for other module functions.