5.1.2 Hardware

Specifications

Specification Description

Form Factor

Single Slot 1771 chassis compatible
BTR/BTW data transfer

Local or remote rack

Backplane current load

800 mA @ 5 V

Operating temperature

0 to 60°C (32 to 140°F)

Storage temperature

-40 to 85°C (-40 to 185°F)

Shock 30g

operational

50g non-operational

Vibration

5 g from 10150 Hz

Relative humidity

5% to 95% (non-condensing)

LED Indicators

Module status

Backplane transfer status

Application status

Serial activity and error LED status

Configuration Serial port (CFG)

DB-9M PC compatible

RS-232

Hardware handshaking

Ethernet Port (Ethernet modules)

RJ45 Connector

Link and activity LED indicators

Electrical Isolation 1500 V rms at 50 Hz to 60 Hz for 60 s,
applied as specified in section 5.3.2 of IEC 60950: 1991

Ethernet Broadcast Storm Resiliency = less than or equal to
5000 [ARP] frames-per-second and less than or equal to 5
minutes duration

5.1.3 Functional

Specifications

ƒ 10/100 MB Ethernet Application port
ƒ Supports Enron version of Modbus protocol for floating point data

transactions

ƒ PCB includes a powerful Modbus network analyzer
ƒ Special functions (command control, event commands, status, etc.) are

supported by message transfer (unscheduled) using the MSG instruction

ƒ Configurable parameters for the client including a minimum response delay of

0 to 65535 ms and floating point support

ƒ Supports five independent server connections for Service Port 502
ƒ Supports five independent server connections for Service Port 2000
ƒ All data mapping begins at Modbus register 40001.
ƒ Error codes, network error counters, and port status data available in user

data memory