Force single coil (function code 05) – ProSoft Technology MVI71-MNET User Manual

Page 91

Advertising
background image

Reference MVI71-MNET

♦ PLC Platform

User Manual

Modbus TCP/IP Interface Module


ProSoft Technology, Inc.

Page 91 of 109

June 23, 2009

Response

The addressed Slave responds with its address and the function code followed
by the information field. The information field contains 1 byte describing the
quantity of data bytes to be returned. The contents of the registers requested
(DATA) are 2 bytes each, with the binary content right justified within each pair of
characters. The first byte includes the high order bits and the second, the low
order bits.

Because the Slave interface is normally serviced at the end of the controller's
scan, the data will reflect the register content at the end of the scan. Each PC will
limit the quantity of register contents provided each scan; thus for large register
quantities, multiple PC scans will be required, and the data provided will be form
sequential scans.

In the example below the register 3009 contains the decimal value 0.

Adr

Func

Byte Count

Data Input Reg Hi

Data Input Reg Lo

Error Check Field

11 04 02

00

00

E9

5.7.5 Force Single Coil (Function Code 05)

Query
This message forces a single coil either ON or OFF. Any coil that exists within
the controller can be forced to either state (ON or OFF). However, because the
controller is actively scanning, unless the coil is disabled, the controller can also
alter the state of the coil. Coils are numbered from zero (coil 0001 = zero, coil
0002 = one, and so on). The data value 65,280 (FF00 HEX) will set the coil ON
and the value zero will turn it OFF; all other values are illegal and will not affect
that coil.

The use of Slave address 00 (Broadcast Mode) will force all attached Slaves to
modify the desired coil.

Note: Functions 5, 6, 15, and 16 are the only messages that will be recognized as valid for
broadcast.

The example below is a request to Slave number 11 to turn ON coil 0173.

Adr

Func

Data Coil # Hi

Data Coil # Lo

Data On/off Ind

Data

Error Check Field

11 05 00

AC

FF

00

CRC

Response

The normal response to the Command Request is to re-transmit the message as
received after the coil state has been altered.

Adr

Func

Data Coil # Hi

Data Coil # Lo

Data On/ Off

Data

Error Check Field

11 05

00

AC

FF

00

CRC

The forcing of a coil via MODBUS function 5 will be accomplished regardless of
whether the addressed coil is disabled or not (In ProSoft products, the coil is only
affected if the necessary ladder logic is implemented).