Preset multiple registers (function code 16) – ProSoft Technology MVI71-MNET User Manual

Page 95

Advertising
background image

Reference MVI71-MNET

♦ PLC Platform

User Manual

Modbus TCP/IP Interface Module


ProSoft Technology, Inc.

Page 95 of 109

June 23, 2009

Note: Functions 5, 6, 15, and 16 are the only messages (other than Loopback Diagnostic Test) that
will be recognized as valid for broadcast.

The following example forces 10 coils starting at address 20 (13 HEX). The two
data fields, CD =1100 and 00 = 0000 000, indicate that coils 27, 26, 23, 22, and
20 are to be forced on.

Adr

Func

Hi Add Lo Add Quantity Byte

Cnt

Data Coil Status
20 to 27

Data Coil Status
28 to 29

Error Check
Field

11 0F 00 13 00

0A 02

CD

00 CRC

Response

The normal response will be an echo of the Slave address, function code,
starting address, and quantity of coils forced.

Adr

Func

Hi Addr

Lo Addr

Quantity

Error Check Field

11 0F 00 13 00 0A CRC

The writing of coils via Modbus function 15 will be accomplished regardless of
whether the addressed coils are disabled or not.

Coils that are unprogrammed in the controller logic program are not automatically
cleared upon power up. Thus, if such a coil is set ON by function code 15 and
(even months later) an output is connected to that coil, the output will be hot.

5.7.9 Preset

Multiple

Registers (Function Code 16)

Query

Holding registers existing within the controller can have their contents changed
by this message (a maximum of 60 registers). However, because the controller is
actively scanning, it also can alter the content of any holding register at any time.
The values are provided in binary up to the maximum capacity of the controller
(16-bit for the 184/384 and 584); unused high order bits must be set to zero.
When specified registers with contents specified.

Note: Function codes 5, 6, 15, and 16 are the only messages that will be recognized as valid for
broadcast.

Adr Func Hi

Add

Lo Add Quantity

Byte
Cnt

Hi
Data

Lo
Data

Hi
Data

Lo
Data

Error Check
Field

11

10 00

87

00 02

04 00 0A

01 02 CRC

Response

The normal response to a function 16 query is to echo the address, function
code, starting address and number of registers to be loaded.

Adr

Func

Hi Addr

Lo Addr

Quantity

Error Check Field

11

10 00 87 00

02

56