00 return query data, Example and state diagram – ProSoft Technology MVI71-MNET User Manual

Page 93

Advertising
background image

Reference MVI71-MNET

♦ PLC Platform

User Manual

Modbus TCP/IP Interface Module


ProSoft Technology, Inc.

Page 93 of 109

June 23, 2009

A server device can, however, be forced into 'Listen Only Mode' in which it will
monitor the messages on the communications system but not respond to them.
This can affect the outcome of your application program if it depends upon any
further exchange of data with the remote device. Generally, the mode is forced to
remove a malfunctioning remote device from the communications system.

The following diagnostic functions are dedicated to serial line devices.

The normal response to the Return Query Data request is to loopback the same
data. The function code and sub-function codes are also echoed.

Request

Function code

1 Byte

0x08

Sub-function 2

Bytes

Data

N x 2 Bytes

Response

Function code

1 Byte

0x08

Sub-function 2

Bytes

Data

N x 2 Bytes

Error

Error code

1 Byte

0x88

Exception code

1 Byte

01 or 03 or 04

Sub-function codes supported by the serial line devices

Only Sub-functions 00 is supported by the MVI71-MNET module.

00 Return Query Data

The data passed in the request data field is to be returned (looped back) in the
response. The entire response message should be identical to the request.

Sub-function

Data Field (Request)

Data Field (Response)

00 00

Any

Echo Request Data

Example and state diagram

Here is an example of a request to remote device to Return Query Data. This
uses a sub-function code of zero (00 00 hex in the two-byte field). The data to be
returned is sent in the two-byte data field (A5 37 hex).

Request

Response

Field Name

(Hex)

Field Name

(Hex)

Function 08

Function 08

Sub-function Hi

00

Sub-function Hi

00

Sub-function Lo

00

Sub-function Lo

00

Data Hi

A5

Data Hi

A5

Data Lo

37

Data Lo

27