E. vent diagrams, One elbow, Top vent - horizontal termination - (continued) – Hearth and Home Technologies Direct Vent Gas Appliance EDV3633L User Manual

Page 25

Advertising
background image

Heatilator • Eclipse • 4049-229 Rev F • 11/08

25

To replace the fi rst starter elbow with two 45° elbows,
refer to Figure 7.4. All other 90° elbows can be replaced
with two 45° elbows.
General Rules:
• SUBTRACT 3 ft. from the total H measurement for each

90° elbow installed horizontally.

• SUBTRACT 1-1/2 ft. from the total H measurement for

each 45° elbow installed horizontally.

• A maximum of three 90° elbows (or six 45° elbows)

may be used in any vent confi guration. Some elbows
may be installed horizontally. See Figure 7.9.

• Elbows may be placed back to back anywhere in the

system as long as the fi rst 90° elbow is a starter elbow
except as shown in Figure 7.4.

• When penetrating a combustible wall, a wall shield

fi restop must be installed on both sides.

• When penetrating a combustible ceiling, a ceiling

fi restop must be installed.

• Horizontal runs of vent do not require vertical rise;

horizontal runs may be level.

E. Vent Diagrams

Figure 7.3

One Elbow

V

1

H

1

1. Top Vent - Horizontal Termination - (continued)

V

1

min.

V

1

max.

H

1

max.

ft

m

ft

m

ft

m

0*

-

-

1.67

0.51

0.5

0.15

-

-

6

1.83

1

0.30

-

-

11

3.35

1.5

0.46

-

-

18

5.49

2

0.61

-

-

25

7.62

-

-

25

7.62

25

7.62

* You may install elbow directly on top of appliance.