Finishing, A. mantel and wall projections, B. facing material – Hearth and Home Technologies Direct Vent Gas Appliance EDV3633L User Manual

Page 45: Mantels combustible mantel legs/wall projections

Advertising
background image

Heatilator • Eclipse • 4049-229 Rev F • 11/08

45

A 2 in. (51 mm) min.

from fireplace opening
to perpendicular wall

Mantel Leg or

Perpendicular Wall

Top of
Appliance

Drywall

A

Measured from top of fireplace opening (in inches)

3

4

5

6

7

8

9

10

11

12

13

14

15

16

17

18

8-3/4

9-1/2

10-1/4

11

11-3/4

12-1/2

13-1/4

14

14-3/4

15-1/2

16-1/4

17

17-3/4

18-1/2

19-1/4

20

30 in. minimum

to ceiling

13

13

Finishing

A. Mantel and Wall Projections

WARNING! Risk of Fire! Comply with all minimum clear-
ances to combustibles as specifi ed. Framing or fi nishing
material closer than the minimums listed must be construct-
ed entirely of noncombustible materials (i.e., steel studs,
concrete board, etc).

Figure 13.1 Minimum Vertical and Maximum Horizontal
Dimensions

Note: All
measurements
in inches.

Figure 13.2 Mantel Leg or Wall Projections (Acceptable on both
sides of opening)

Mantels

Combustible Mantel Legs/Wall Projections

0 in.

0 in.

0 in.

Finish wall material may be
combustible - Top and Sides

High Temperature Sealant (300° F/149° C min.)

Top and Side Seal Joint

B. Facing Material

• Metal front faces may be covered with non-combustible

materials only.

• Facing

and/or

fi nishing materials must not interfere with

air fl ow through louvers, operation of louvers or doors,
or access for service.

• Facing

and/or

fi nishing materials must never overhang

into the glass opening.

• Observe all clearances when applying combustible

materials.

• Seal joints between the fi nished wall and appliance top

and sides using a 300 °F minimum sealant. Refer to
Figure 13.3.

WARNING! Risk of Fire! DO NOT apply combustible ma-
terials beyond the minimum clearances. Comply with all
minimum clearances to combustibles as specifi ed in this
manual. Overlapping materials could ignite and will inter-
fere with proper operation of doors and louvers.

Figure 13.3 Noncombustible Facing Diagram