C. Install the Ceiling Firestop

A ceiling fi restop MUST be used between
fl oors and attics.

• Frame opening 9 in. x 9 in. (229 mm x

229 mm) whenever the vent penetrates
a ceiling/floor (see Figure 8.3).

• Frame the area with the same sized lumber

as used in ceiling/fl oor joist.

• The

ceiling

fi restop may be installed above

or below the ceiling joists when installed
with a attic insulation shield. It must be
under joists between fl oors that are not
insulated. Refer to Figure 8.4.

• Secure with three fasteners on each side.

WARNING! Risk of Fire! DO NOT pack
insulation around the vent. Insulation must be
kept back from the pipe to prevent overheat-
ing.

Figure 8.3 Installing Ceiling Firestop

Figure 8.4 Installing the Attic Shield