Hearth and Home Technologies Direct Vent Gas Appliance EDV3633L User Manual

Page 40

Advertising
background image

Heatilator • Eclipse • 4049-229 Rev F • 11/08

40

INTERIOR

Heat Shield or

Extended

Heat Shield

Wall Shield

Firestop

Heat Shield

1-1/2 in. (38 mm) min.

overlap

SHEATHING

Vent depth from back of appliance to

outside surface of exterior wall

(see chart below)

Slip Section

can be extended

Inner Vent

Outer Vent

EXTERIOR

Figure 10.17 Venting through the wall

Note: When using termination caps with factory-supplied
heat shield attached, no additional wall shield fi restop is
required on the exterior side of a combustible wall.

Install Horizontal Termination Cap

WARNING! Risk of Fire! The telescoping fl ue section
of the termination cap MUST be used when connecting
vent.

• 1-1/2 (38 mm) minimum overlap of fl ue telescoping

section is required.

Failure to maintain overlap may cause overheating and
fi re.

• Vent termination must not be recessed in the wall. Siding

may be brought to the edge of the cap base.

• Flash and seal as appropriate for siding material at

outside edges of cap.

• When installing a horizontal termination cap, follow

the cap location guidelines as prescribed by current
ANSI Z223.1 and CAN/CGA-B149 installation codes
and refer to Section 6 of this manual.

CAUTION! Risk of Burns! Local codes may require
installation of a cap shield to prevent anything or anyone
from touching the hot cap.

NOTICE: For certain exposures which require superior
resistance to wind-driven rain penetration, a fl ashing kit and
HRC caps are available. When penetrating a brick wall, a
brick extension kit is available for framing the brick.

Cap Specifi cation Chart (depth without

using additional pipe sections)

EDV Series

SLP-TRAP1

Top Vent Depth

2 to 3 7/8 in.

SLP-TRAP2

Top Vent Depth

4 3/8 to 8 3/8 in.

SLP-TRAP1 can adjust 1 5/8 in. (3 1/8 to 4 3/4)

SLP-TRAP2 can adjust 4 in. (5 1/4 to 9 1/4)