E. Installing Metal Roof Flashing

Note: Skip this section if using the RF4-8.
• See minimum vent heights for various pitched roofs

(Figure 10.8) to determine the length of pipe to extend
through the roof.

• Slide the roof fl ashing over the pipe sections extending

through the roof as shown in Figure 10.9.

Horizontal
overhang

12

X

20 in.

(508 mm)

Lowest

Discharge

Opening

Termination

Cap

Roof Pitch
is X / 12

Vertical
wall

H (min.) - Minimum height
from roof to lowest
discharge opening.

24 in. min.

(610 mm)

Roof Pitch

H (Min.) Ft.

Roof Pitch

H (Min.) Ft.

Flat to 6/12

1.0*

Over 11/12 to 12/12

4.0

Over 6/12 to 7/12

1.25*

Over 12/12 to 14/12

5.0

Over 7/12 to 8/12

1.5*

Over 14/12 to 16/12

6.0

Over 8/12 to 9/12

2.0*

Over 16/12 to 18/12

7.0

Over 9/12 to 10/12

2.5

Over 18/12 to 20/12

7.5

Over 10/12 to 11/12 3.25

Over 20/12 to 21/12

8.0

* 3 ft. minimum in snow regions

Storm Collar

Roof

Flashing

Figure 10.8 Minimum Height From Roof To Lowest Discharge

Opening

Figure 10.9

NOTICE: Failure to properly caulk the roof fl ashing could
cause water entry.

• Caulk the gap between the roof fl ashing and the outside

diameter of the pipe.

• Caulk the perimeter of the fl ashing where it contacts the

roof surface. See Figure 10.9.

Caulk

Pipe

Flashing