Heat & Glo • Cyclone-BN, Cyclone-BC • 2073-900 Rev. N • 10/08

13

V

T

H

T

Figure 5.3

Figure 5.4

D. Vent Diagrams

1. Top Vent - Horizontal Termination

One Elbow

Two Elbows

H

2

H

1

V

T

Fire Risk. Explosion Risk.

Do NOT pack insulation or other combustibles between ceiling fi restops.

• ALWAYS maintain specifi ed clearances around venting and fi restop systems.

• Install wall shield and ceiling fi restops as specifi ed.

Failure to keep insulation or other material away from vent pipe may cause fi re.

WARNING

V

T

Min.

H

T

Max.

1.5 ft.

2 ft.

2.5 ft.

5 ft.

3.5 ft.

8 ft.

4.5 ft.

11 ft.

V

T

+ H

T

= 40 ft. Max

H

1

H

2

V

T

Min.

H

T

Max.

*

*

1.5 ft.

2 ft.

*

*

2.5 ft.

5 ft.

*

*

3.5 ft.

8 ft.

*

*

4.5 ft.

11 ft.

V

T

+ H

T

= 40 ft. Max.

*No specifi c restrictions on this value

EXCEPT V

T

+ HT cannot exceed 40 ft. Max.

NOTE: There MUST be a 25%
reduction in total H when using
fl ex vent except when using the
simple up and out installation
(see Figure 5.7).

NOTE: There MUST be a 25%
reduction in total H when using
fl ex vent except when using the
simple up and out installation
(see Figure 5.7).