Vent clearances and framing, Warning, A. pipe clearances to combustibles – Hearth and Home Technologies Cyclone-BC User Manual

Page 17: B. wall penetration framing

Advertising
background image

Heat & Glo • Cyclone-BN, Cyclone-BC • 2073-900 Rev. N • 10/08

17

A. Pipe Clearances to Combustibles

6

6

Vent Clearances and Framing

Fire Risk.

Explosion Risk.

Maintain vent clearance to combustibles as
specifi ed.

• Do not pack air space with insulation or

other materials.

Failure to keep insulation or other materials
away from vent pipe may cause fi re.

Figure 6.2 Exterior Wall Hole

A

Do NOT pack

with insulation or

other materials.

B

C*

* TO CENTER OF
FRAMING HOLE

WARNING

SL Pipe Clearances to Combustibles

A

B

C

Inches

10

10

66-1/2

mm

254

254

1689

Note: Heat shields MUST overlap by a minimum of 1-1/2 in. (38 mm).

SLP heat shield - designed to be used on a wall 4-3/8 in. to 7-5/8

in. (111 mm to 194 mm thick).

• If wall thickness is less than 4-3/8 the existing heat shields must be

field trimmed. If wall thickness is greater than 7-5/8 in. a DVP-
HSM-B will be required.

2-1/2 in. (64 mm)

top clearance at

wall shield firestops

1/2 in. (13 mm) bottom
clearance at wall
shield firestops

1 in. (25 mm)
clearance
bottom and sides

Heat

Shields

Wall

Shield

Firestop

WALL

3 in. (76 mm)

top clearance

1 in. (25 mm)
clearance around
vertical sections

Figure 6.1 Horizontal venting clearances to combustible
materials

B. Wall Penetration Framing

Combustible Wall Penetration

Whenever a combustible wall is penetrated, you must
frame a hole for the wall shield fi restop. The wall shield
fi restop maintains minimum clearances and prevents cold
air infi ltration.

• The opening must be framed on all four sides using the

same size framing materials as those used in the wall
construction.

• SLP pipe - A wall shield fi restop must be placed on each

side of an interior wall. A minimum 1-1/2 in. (38 mm)
overlap of attached heat shields must be maintained.

• See Section 8.L. for information for regarding the instal-

lation of a horizontal termination cap.

Non-Combustible Wall Penetration

If the hole being penetrated is surrounded by noncombus-
tible materials such as concrete, a hole with diameter one
in. greater than the pipe is acceptable.

Whenever a non-combustible wall is penetrated, the wall
shield fi restop is only required on one side and no heat
shield is necessary.

Advertising
This manual is related to the following products: