Hearth and Home Technologies Cyclone-BC User Manual

Page 22

Advertising
background image

Heat & Glo • Cyclone-BN, Cyclone-BC • 2073-900 Rev. N • 10/08

22

B. Assemble Slip Sections

• Slide the inner fl ue of the slip section into the inner fl ue

of the pipe section and the outer fl ue of the slip section
over the outer fl ue of the pipe section. See Figure 8.3.

• Slide together to the desired length.

Figure 8.3 Slip Section Pilot Holes

Figure 8.4 Screws into Slip Section

Pilot hole

Pilot hole

• Continue adding pipe as necessary following instructions

in “Assembling Pipe Sections.”

NOTICE: If slip section is too long, the inner and outer fl ues
of the slip section can be cut to the desired length.

NOTICE: When installing a vent system with an HRC
termination cap, all pipe system joints shall be sealed using
a high temperature silicone sealant.

• Apply a bead of silicone sealant inside the female outer

pipe joint prior to joining sections.

• Only outer pipes are sealed, sealing the inner fl ue is not

required.

• All unit collar, pipe, slip section, elbow and cap outer

fl ues shall be sealed.

• Maintain a 1-1/2 in. (38 mm) overlap between the slip

section and the pipe section.

• Secure the pipe and slip section with two screws no

longer than 1/2 in. (13 mm), using the pilot holes in the
slip section. See Figure 8.4.

Figure 8.5 Securing Vertical Pipe Sections

Figure 8.6 Securing Horizontal Pipe Sections

C. Secure the Vent Sections

• Vertical runs of SLP pipe must be supported every 8 ft.

(2.44 m).

• Horizontal sections must be supported every 5 feet

(1.52 m).

• Vent supports or plumbers strap (spaced 120º apart)

may be used to support. See Figures 8.5 and 8.6.

• Wall shield fi restops may be used to provide horizontal

support.

• SLP ceiling fi restops have tabs that may be used to

provide vertical support.

WARNING! Risk of Fire, Explosion or Asphyxiation!
Improper support may allow vent to sag and separate.
Use vent run supports and connect vent sections per in-
stallation instructions. DO NOT allow vent to sag below
connection point to appliance.