2 environmental specifications, 3 type tests, Nvironmental – GE MULTILINK ML2400 User Manual

Page 15: Pecifications, Ests

Advertising
background image

CHAPTER 1: INTRODUCTION

INTRODUCTION

MULTILINK ML2400 ETHERNET COMMUNICATIONS SWITCH – INSTRUCTION MANUAL

1–5

1.3.2

Environmental Specifications

OPERATING ENVIRONMENT

Ambient temperature: .................................–40 to 185°F (–40 to 85°C) for IEC 60068-2-1, IEC 60068-

2-2 for 16 hours
Nominal

≤ 50°C

Storage temperature:...................................–60 to 210°F (–50 to 100°C)
Ambient relative humidity: ........................5% to 95% (non-condensing)
Altitude:...............................................................2000 m

1.3.3

Type Tests

Standard Name

Standard Number:Date code

Severity levels Tested

Electrostatic Discharge: Air

and Direct

EN/IEC61000-4-2:1995

8Kv contact,15Kv Air (Level 4)

Electrostatic Discharge: Air

and Direct

IEEE C37.90.3:2001

8Kvcontact,15Kv air

Electrical Fast Transient/

Burst Immunity

EN/IEC61000-4-4:2004

(+/-4KV @2.5Khz for Common and Transverse

modes) & 2KV 5Khz Common and transverse

(Level 3 & 4)

Electrical Fast Transient/

Burst Immunity

IEEE C37.90.1:2002

Class 4 (+/-4KV for Common and Transverse

modes)

Power Transients )high

repetition

NEMA TS2 2.1.6.1:2003

300V,2500W

Power Transients (low

repetition high energy)

NEMA TS2 :2003

600V, 1 ohm impedance

Transients I/O terminals

NEMA TS2 2.1.7.1 :2003

300V,1000ohms impedance

Surge Immunity

IEC61000-4-5:2005

Class 4 (2KV Line to Earth and 1KV Line to Line)

Installation Class 3, Level 2 & 3

Non Destructive transient

Immunity

NEMA TS2:2003

1000V,1 ohm X 3

Ring Wave Surge ,IEC

Damped Oscillatory Burst

1Mhz

EN/IEC61000-4-12 :2006

Ring wave: (1KV Common), 0.5KV (diff) (Level 2)

SWC Damped Oscillatory

IEEEC37.90.1:2002

Common and transverse to 2.5KV, No Transverse

for Data Comms and Signal cct

Voltage Dip; 2. Voltage

Interruption;

EN/IEC 61000-4-11 :2004

0%(5000msec),40%(6 cycles), 70%(10msec) of

test voltage

Ripple on DC power I/P port

IEC 61000-4-17

10% of rated voltage (Level 3)

RF Immunity 80-1000MHz

EN/IEC 61000-4-3 :1998

10V/m (Level 3)

RF Immunity 80-1000MHz

IEEE C37.90.2:2004

35V/m (20V/m + modulation)

Conducted RF Immunity

150Khz -80 MHz

IEC61000-4-6:1996

10Vrms (Level 3)

Conducted RF Immunity 0-

150Khz

EN/IEC 61000-4-16:1998

15Hz-150 Khz 1-10V (Level 3)

Power Frequency Magnetic

Field Immunity

EN/IEC 61000-4-8:1993,2001

continuous 100/200A/m (Level 5 - continuous)

Damped magnetic Immunity IEC61000-4-10

10A/m (Level 3)

Voltage dips and Interrupts

for DC power ports

IEC61000-4-29

All test levels and durations - Passes to Criteria B

Conducted & Radiated

Emissions

CISPR22 / EN 55022

Class A

Conducted & Radiated

Emissions

FCC Part 15 Subpart B

Class A