GE MULTILINK ML2400 User Manual

Page 276

Advertising
background image

17–4

MULTILINK ML2400 ETHERNET COMMUNICATIONS SWITCH – INSTRUCTION MANUAL

MISCELLANEOUS COMMANDS

CHAPTER 17: MISCELLANEOUS COMMANDS

Example 17-1: Alarm relays

ML2400#

alarm

ML2400(alarm)##

add event=2

Alarm Event(s) Added: 2

ML2400(alarm)##

add event=1-5

Event 2 is Already Enabled.

Alarm Event(s) Added: 1, 3, 4, 5

ML2400(alarm)##

add event=6,8

Alarm Event(s) Added: 6, 8

ML2400(alarm)##

add event=all

Event 1 is Already Enabled.

Event 2 is Already Enabled.

Event 3 is Already Enabled.

Event 4 is Already Enabled.

Event 5 is Already Enabled.

Event 6 is Already Enabled.

Event 8 is Already Enabled.

Alarm Event(s) Added: 7, 9, 10, 11, 12

ML2400(alarm)##

del event=2

Alarm Event(s) Deleted: 2

ML2400

(alarm)##

period time=5

Relay closure Time Set.

ML2400(alarm)##

show alarm

Alarm Events Configuration

--------------------------

Alarm Status: DISABLED

Relay Closure Time Period: 5 Seconds

EventId

Description

Mode

------------------------------------------

1

S-RING OPEN

SUSTAINED

2

Cold Start

NOT ENABLED

3

Warm Start

MOMENTARY

4

Link Up

MOMENTARY

5

Link Down

MOMENTARY

6

Authentication Failure

MOMENTARY

7

RMON Raising Alarm

MOMENTARY

8

RMON Falling Alarm

MOMENTARY

9

Intruder Alarm

MOMENTARY

10

Link Loss Learn Triggered

MOMENTARY

11

Broadcast Storm Detected

MOMENTARY

12

STP/RSTP Reconfigured

MOMENTARY

(continued on next page)