DCa150USJ2 60 hz generator • operation anD partS manUal — rev. #0 (08/22/11) — page 37

engine Operating panel

11.

tachometer – Indicates engine speed in RPM’s for 60

Hz operation. This meter should indicate 1800 RPM’s

when the rated load is applied. In addition a built in hour

meter will record the number of operational hours that

the generator has been in use.

12.

Diagnostic Display – This display monitors crtical engine

functions. If any abnormal conditions occur, an Active

Fault Code will be displayed. This diagnostic display can

be located inside the control box.

13.

engine Speed Switch – This switch controls the speed

of the engine (low/high)

.

14.

auto Start/Stop engine

Controller (eCU) — This controller

has a vertical row of status LED's

(inset), that when lit, indicate

that an engine malfunction (fault)

has been detected. When a fault

has been detected the engine

controller will evaluate the fault

and all major faults will shutdown

the generator. During cranking cycle, the ECU will

attempt to crank the engine for 10 seconds before

disengaging.

If the engine does not engage (start) by the third

attempt, the engine will be shutdown by the engine

controller’s Over Crank Protection mode. If the engine

engages at a speed (RPM's) that is not safe, the

controller will shutdown the engine by initializing the

Over Speed Protection mode.

Also the engine controller will shut down the engine in

the event of low oil pressure, high coolant temperature,

low coolant level, and loss of magnetic pickup.

These conditions can be observed by monitoring the

LED status indicators on the front of the controller

module.

A.

mpeC Control Switch — This switch controls the

running of the unit. If this switch is set to the OFF/

RESET position, the unit will not run. When this switch

is set to the manual position, the generator will start

immediately.

If the generator is to be connected to a building’s

AC power source via an automatic transfer switch

(isolation), place the switch in the AUTO position. In this

position, should an outage occur, the automatic transfer

switch (ATS) will start the generator automatically

via the generator’s auto-start contacts connected to

the ATS’s start contacts. Please refer to your ATS

installation manual for further instructions for the

correct installation of the auto-start contacts of the

generator to the ATS.

B.

low oil pressure — Indicates the engine pressure

has fallen below 15 psi (103 kPa). The oil pressure

is detected using variable resistive values from the

oil pressure sending unit. This is considered a major

fault.

C.

High Coolant Temperature — Indicates the engine

temperature has exceeded 239°F (110°C). The engine

temperature is detected using variable resistive values

from the temperature sending unit. This is considered

a major fault.

D.

Overcrank Shutdown — Indicates the unit has

attempted to start a pre- programmed number of

times, and has failed to start. The number of cycles

and duration are programmable. It is pre-set at 3

cycles with a 10 second duration. This is considered

a major fault.

E.

Overspeed Shutdown — Indicates the engine is

running at an unsafe speed. This is considered a

major fault.

F.

Engine Running — Indicates that engine is running

at a safe operating speed.