Generator start-up procedure – Multiquip MQ Power Whisperwatt 60HZ Generator DCA150USJ2 User Manual

Page 50

Advertising
background image

page 50 — DCa150USJ2 60 hz generator • operation anD partS manUal — rev. #0 (08/22/11)

generatOr start-up prOcedure

BeFore Starting

1. Place the

main, g.F.C.i., and aux. circuit breakers (Figure

37) in the

OFF position prior to starting the engine.

Figure 37. Main, Aux. and GFCI

Circuit Breakers (OFF)

2. Make sure the

voltage change-over board has been

configured for the desired output voltage.

3. Connect the load to the

receptacles or the output

terminal lugs as shown in Figure 12. These load

connection points can be found on the output terminal

panel and the output terminal panel’s hard wire hookup

panel.

4. Tighten terminal nuts securely to prevent load wires

from slipping out.

5. Close all engine enclosure doors (Figure 38).

Figure 38. Engine Enclosure Doors

CaUtion

The engine’s exhaust contains harmful emissions.

alWaYS have adequate ventilation when operating.

Direct exhaust away from nearby personnel.

Warning

never manually start the engine with the main, gFCi or

auxiliary circuit breakers in the ON (closed) position.

INCORRECT

CORRECT

Starting

1. Place the

voltage selector switch in the desired

voltage position (Figure 39)..

Figure 39. Voltage Selector Switch

Starting (manUal)

1. Place the engine speed switch (Figure 40) in the LOW

(down) position.

Figure 40. Engine Speed Switch (Low)

2. Place the

mpeC control switch in the manUal

position to start the engine (Figure 41).

Figure 41. MPEC Control Switch

(Manual Position)

3. Depending on the temperature of the coolant (cold

weather conditions), the pre-heat lamp (Figure 42) will

light (ON) and remain on until the pre-heating cycle has

been completed. After completion of the pre-heating

cycle, the light will go OFF and the engine will start up

automatically.

Figure 42. Pre-Heat Lamp