Generator start-up procedure – Multiquip MQ Power Whisperwatt 60HZ Generator DCA150USJ2 User Manual

Page 51

Advertising
background image

DCa150USJ2 60 hz generator • operation anD partS manUal — rev. #0 (08/22/11) — page 51

generatOr start-up prOcedure

4. Once the engine starts, let the engine run for 1-2

minutes. Listen for any abnormal noises. If any

abnormalities exist, shut down the engine and correct

the problem. If the engine is running smoothly, place

the engine speed switch (Figure 43) in the

high (up)

position.

Figure 43. Engine Speed Switch (High)

5. Verify that the

engine running status LED on the

MPEC module (Figure 44) is lit (ON) after the engine

has started.

Figure 44. Engine Running (LED ON)

6. The generator’s frequency meter (Figure 45) should be

displaying the 50 cycle output frequency in

HERTZ.

Figure 45. Frequency Meter

7. The generator’s AC-voltmeter (Figure 46) will display

the generator’s output in

voltS..

Figure 46. Frequency Meter

8. If the voltage is not within the specified tolerance use

the voltage adjustment control knob (Figure 47) to

increase or decrease the desired voltage.

Figure 47. Voltage Adjust Control Knob

9. The ammeter (Figure 48) will indicate

zero amps with

no load applied. When a load is applied, the ammeter

will indicate the amount of current that the load is

drawing from the generator.

Figure 48. Ammeter (No Load)

10. The engine oil pressure gauge (Figure 49) will indicate

the oil pressure of the engine. Under normal operating

conditions the oil pressure is approximately 42 to 71

psi. (290~490 kPa).

Figure 49. Oil Pressure Gauge

11. The

coolant temperature gauge (Figure 50) will

indicate the coolant temperature. Under normal

operating conditions the coolant temperature should

be between 167°~203°F (75°~95°C) (

Green Zone).

Figure 50. Coolant Temperature Gauge