Marathon Computer UNIPRO V3.5 User Manual

Page 171

Advertising
background image

MMI Product Documentation

Unipro 3.5 Process Control 1 Aug. 1997

Using the [Display] key, select the

proper input to be calibrated (input A, if
standard configuration).

Using the [Enter] key, select the

zero mode (IE: if for input A, Z-A).

Set the calibrator output to the

recommended zero value for the
thermocouple type selected. See the table
below.

Using the Arrow keys, adjust the

process value to equal the calibrator
output.

Press the [Enter] key to select the

span mode (IE: S-A, for input A).

Set the calibrator output to the

recommended span value in for the
thermocouple type selected.

Using the arrow keys, adjust the

process value to equal the calibrator
output.

Repeat steps f. through j. until no

additional change is needed.

Press the [Enter] key one more

time to be sure the calibration factors are
stored. Go to the next input to be
calibrated or exit calibration mode by
removing the calibration jumper or
pressing [Setup] .

Thermocouple type

Zero ºF(ºC)

SpanºF ( C)

B

200 (90)

3000 (1800)

C

32 (0)

3000 (1800)

E

32 (0)

1300 (900)

J

32 (0)

1300 (900)