Setup and Configuration

Unipro 3.5

Rev. 8.00
November 30, 1995

programmed setpoint is at 0.80, the alarm

will trigger at 0.90 and 0.70.)

DEV

Alarm actuation uses DEVIATION

control above or below the programmed

setpoint. The + and - symbols determine if

the deviation is allowed or if it is above (+)

the programmed setpoint or below (-) it.

(i.e. If deviation of 0.10 is placed in the

ALARM VALUE and 0.80 is the

programmed SETPOINT the alarm will

trigger at 0.90 or 0.70, for -0.10.)

FLT

An input FAULT, or a program

alarm is to be used as basis for the actuation.

The ALARM VALUE is ignored.

PRG

An Internal program will actuate the

alarm.

PO

Alarm actuation is based on the

PERCENT OUTPUT exceeding the limit in

the ALARM VALUE .

PV

PROCESS control mode. Alarm

actuation is based on the PROCESS

VARIABLE exceeding the limit in the

ALARM VALUE.